Mitsubishi Electric PQHY/PQRY code 2000

No approved translation for this record yet; showing the original text.

Meaning

Pump interlock error: 1) This error is detected by the pump interlock circuit (TB8 3-4). 2) If it is detected that the pump interlock circuit (TB8 3-4) is open (first detection) during operation or immediately before startup, the heat source unit stops and goes into the 3-minute restart delay mode. 3) If the pump interlock circuit (TB8 3-4) has remained open for continuous 10 minutes (second detection) since the first stoppage of the heat source unit, the unit will make an abnormal stop, and the error code "2000" app

Member details

Signed-in members see the LED pattern and how to read the code with the remote control on eligible records.

View details as a member

Possible causes

(1) Heat source water circulation pump (2) Broken wire (3) Loose connectors or contact failure (4) Interlock signal input circuit fault on (5) Interlock signal input circuit fault on board (6) SW4(917) setting error (7) SW4(901) and SW4(917) setting error