Meaning
TCH070A: Drain pump lock protection operation Error postponement, if drain pump stops 1 for 5 seconds continuously while drain pump is operating. Drain pump is abnormal if above condi 2 tion is repeated 4 times after error post ponement is detected. Freezing/overheating protection is work ing Freezing protection (Cooling mode) 1 • In case when outside temperature > −4°F [−20:] The unit is in 6-minute resume preven tion mode if pipe <liquid or condenser/ evaporator> temperature stays under −5°F [−15:]
Member details
Signed-in members see the LED pattern and how to read the code with the remote control on eligible records.
View details as a memberPossible causes
(1) Malfunction of drain pump (2) Clogged drain pump (3) Contact failure of connector (4) Defective indoor controller board (Cooling or drying mode) (1) Clogged filter (reduced airflow) (2) Short cycle of air path (3) Low-load (low temperature) operation out of the tolerance range (4) Defective indoor fan motor • Fan motor is defective. • Indoor controller board is defec tive. (5) Defective outdoor fan control (6) Overcharge of refrigerant (7) Defective refrigerant circuit (clogs) ( (Heating mode) (3) Overload (high temperature) operation out of the tolerance range (7) Defective refrigerant circuit (clogs) (8) Bypass circuit of outdoor unit is defective. 27
Solution
Solution steps are not shared for faults that may be dangerous.
No do-it-yourself solution is given for this fault. For your safety, call an authorised service.