Mitsubishi Electric PLA code P4

No approved translation for this record yet; showing the original text.

Meaning

Abnormality of drain sensor (DS) Suspensive abnormality, if short/open of 1 thermistor is detected for 30 seconds continuously. (The unit returns to normal operation, if it has normally reset.) Detect the following condition. 3 • During cooling and drying operation. • In case that pipe <liquid> temperature - room temperature <-10deg (Except defrosting) • When pipe <liquid> temp

Member details

Signed-in members see the LED pattern and how to read the code with the remote control on eligible records.

View details as a member

Possible causes

(1) Defective thermistor characteristics (2) Contact failure of connector (CN31) on the indoor controller board. (Insert failure). (3) Breaking of wire or contact failure of drain sensor wiring. (4) Defective indoor controller board.

Solution

Solution steps are not shared for faults that may be dangerous.