Skip to content
RemFixitSearch fault code

Error code

Mitsubishi Electric PLA code E0

No approved translation for this record yet; showing the original text.

Meaning

Remote controller transmission error(E0)/signal receiving error(E4) Abnormal if main or sub remote con1 troller cannot receive any transmission normally from indoor unit of refrigerant address “0” for 3 minutes. (Error code : E0) Abnormal if sub remote controller could 2 not receive for any signal for 2 minutes. (Error code: E0) Abnormal if indoor controller board 1 cannot receive any data normally from remote controller board or from other indoor controller board for 3 minutes.

Member details

Signed-in members see the LED pattern and how to read the code with the remote control on eligible records.

View details as a member

Possible causes

(1) Contact failure at transmission wire of remote controller (2) All remote controllers are set as “sub” remote controller. In this case, E0 is displayed on remote controller, and E4 is displayed at LED (LED1, LED2) on the outdoor controller circuit board. (3) Miswiring of remote controller (4) Defective transmitting receiving circuit of remote controller (5) Defective transmitting receiving circuit of indoor controller board of refrigerant addresses “0”.

Solution

Solution steps are not shared for faults that may be dangerous.

No do-it-yourself solution is given for this fault. For your safety, call an authorised service.

Remote technician support

Get help from a technician over a video call.