Skip to content
RemFixitSearch fault code

Error code

Mitsubishi Electric PFD code 7102

No approved translation for this record yet; showing the original text.

Meaning

Connected unit count over Number of units connected in the same refrigerant system exceeds limitations. Trouble source: Outdoor unit

Member details

Signed-in members see the LED pattern and how to read the code with the remote control on eligible records.

View details as a member

Possible causes

(1) Number of unit connected to terminal block (TB3) for outdoor/indoor transmission line exceeds limitations given be-lows: Item Limitation Total of 1 Indoor unit (2) The Outdoor unit address is being set to 51~100 under automatic address mode (Remote controller displays “HO”). (3) Slipping off of transmission wiring at Outdoor unit. (4) Short circuit of transmission line in case of 3) & 4), remote controller displays “HO”.

Solution

Solution steps are not shared for faults that may be dangerous.

No do-it-yourself solution is given for this fault. For your safety, call an authorised service.

Remote technician support

Get help from a technician over a video call.