Meaning

MA controller signal reception error (No signal reception): ŒCommunication between the MA remote controller and the indoor unit is not done properly. ŒNo proper data has been received for 3 minutes.

Member details

Signed-in members see the LED pattern and how to read the code with the remote control on eligible records.

View details as a member

Possible causes

(1) Contact failure of the remote controller lines of MA remote controller or the indoor unit. (2) All the remote controllers are set to SUB. (3) Failure to meet wiring regulations ŒWire length ŒWire size ŒNumber of remote controllers ŒNumber of indoor units (4) The remote controller is removed after the installation without turning the power source off. (5) Noise interference on the remote controller transmission lines (6) Faulty circuit that is on the indoor board and performs transmission/ reception of the signal from the remote controller (7) Problems with the circuit on the remote controller that sends or receives the signals from the remote controller