Error code
Mitsubishi Electric PFD code 5201
No approved translation for this record yet; showing the original text.
Meaning
High-pressure sensor fault (63HS1): If the high-pressure sensor detects a pressure of 0.098MPa [14psi] or below during operation, the outdoor unit stops, goes into the 20-second restart delay mode, and restarts if the pressure reaches above 0.098MPa [14psi] at the end of the restart delay mode. If the high pressure sensor detects 0.098MPa [14psi] or less just before the restart, the outdoor unit makes an error stop, and the error code "5201" will appear. When the unit is in the 20-second restart delay mode, a preliminary error
Member details
Signed-in members see the LED pattern and how to read the code with the remote control on eligible records.
View details as a memberPossible causes
(1) High pressure sensor failure (2) Pressure drop due to refrigerant leak (3) Torn wire coating (4) A pin on the male connector is missing or contact failure (5) Disconnected wire (6) High pressure sensor input circuit failure on the control board
Solution
Solution steps are not shared for faults that may be dangerous.
No do-it-yourself solution is given for this fault. For your safety, call an authorised service.
Remote technician support
Get help from a technician over a video call.