Mitsubishi Electric PFD code 2502
No approved translation for this record yet; showing the original text.
Meaning
Drain pump abnormality: When indirect heater of drain sensor is turned on, rise in temperature is 20 deg. or less (in water) for 40 seconds, compared with the temperature detected before turning on the indirect heater.
Member details
Signed-in members see the LED pattern and how to read the code with the remote control on eligible records.
View details as a memberPossible causes
(1) Drain sensor sinks in water because drain water level rises due to drain water lifting-up mechanism trouble. (2) Broken wire of indirect heater of drain sensor. (3) Detecting circuit (circuit board) trouble.