Skip to content
RemFixitSearch fault code

Error code

Mitsubishi Electric PFD code 1111

For your safety

This fault is rated critical. No remote repair or do-it-yourself instructions are given; do not use the appliance or try to open or repair it.

Hazard area: refrigerant gas circuit

If there is a risk to life, first move to a safe place, then call 112. Do not follow remote repair instructions.

Call 112

The emergency numbers here are for Turkey. If you are outside Turkey, call your local emergency number.

All emergency numbers and province details

No approved translation for this record yet; showing the original text.

Meaning

Low pressure saturation temperature sensor abnormality (TH2): 1. When saturation temperature sensor (TH2) or liquid level detecting temperature sensors (TH3, TH4) detects -40˚C or less (the first time) during operations, outdoor unit stops once, mode is changed to restart mode after 3 minutes, then the outdoor unit restarts. 2. When -40˚C or less temp. is detected again (the second time) within 30 minutes after stop of outdoor unit, error stop is observed with code Nos. “1111,” “1112,” or “1113” displayed.

Member details

Signed-in members see the LED pattern and how to read the code with the remote control on eligible records.

View details as a member

Possible causes

(1) Gas leak, Gas shortage. (2) Insufficient load operations. (3) Poor operations of indoor LEV. (4) Poor operations of OC controller LEV: (5) Setting error of connection address.

Solution

Solution steps are not shared for faults that may be dangerous.

No do-it-yourself solution is given for this fault. For your safety, call an authorised service.