Error code
Mitsubishi Electric PFD/PUHY code 4109
No approved translation for this record yet; showing the original text.
Meaning
Abnormal fan (IC): If the auxiliary relay X4 (for detecting fan abnormality) is not excited for a certain period of time, the fan makes an error stop, and the fan output turns to OFF. Set value of overcurrent circuit breaker Model, motor output Set value P250 model3.7kW 7.5A PFD P500 model5.5kW 12A
Member details
Signed-in members see the LED pattern and how to read the code with the remote control on eligible records.
View details as a memberPossible causes
(1) Overcurrent circuit breaker (51F) trip (2) A fuse (F1) is blown. (3) Auxiliary relay (X4) failure (4) Broken wire (5) Disconnected wire (6) Indoor controller (I.B1, I.B2) failure
Solution
Solution steps are available to members and are not shown on this page. Answer the questions to open the solution.
Remote technician support
Get help from a technician over a video call.
Address of this page: https://www.remfixit.com/tr/mitsubishi-electric/pfd-puhy/4109