Mitsubishi Electric PFD/PQHY code 4109

No approved translation for this record yet; showing the original text.

Meaning

Abnormal fan (IC): If the auxiliary relay X4 (for detecting fan abnormality) is not excited for a certain period of time, the fan makes an error stop, and the fan output turns to OFF. Set value of overcurrent circuit breaker Model, motor output Set value P250 model3.7kW 7.5A PFD P500 model5.5kW 12A

Member details

Signed-in members see the LED pattern and how to read the code with the remote control on eligible records.

View details as a member

Possible causes

(1) Overcurrent circuit breaker (51F) trip (2) A fuse (F1) is blown. (3) Auxiliary relay (X4) failure (4) Broken wire (5) Disconnected wire (6) Indoor controller (I.B1, I.B2) failure

Solution

Solution steps are available to members and are not shown on this page. Answer the questions to open the solution.

Remote technician support

Get help from a technician over a video call.