Mitsubishi Electric PAC code UL

No approved translation for this record yet; showing the original text.

Meaning

Low pressure (63L operated) Abnormal if 63L is operated (under –0.03MPa [–4.35PSIG]) during compressor operation. 63L: Low-pressure switch

Member details

Signed-in members see the LED pattern and how to read the code with the remote control on eligible records.

View details as a member

Possible causes

(1) Stop valve of outdoor unit is closed during operation. (2) Disconnection or loose connection of connector (63L) on outdoor controller board (3) Disconnection or loose connection of 63L (4) Defective outdoor controller board (5) Leakage or shortage of refrigerant (6) Malfunction of linear expansion valve

Solution

Solution steps are not shared for faults that may be dangerous.

No do-it-yourself solution is given for this fault. For your safety, call an authorised service.

Remote technician support

Get help from a technician over a video call.