Error code
Mitsubishi Electric PAC code UL
No approved translation for this record yet; showing the original text.
Meaning
Low pressure (63L operated) Abnormal if 63L is operated (under –0.03MPa [–4.35PSIG]) during compressor operation. 63L: Low-pressure switch
Member details
Signed-in members see the LED pattern and how to read the code with the remote control on eligible records.
View details as a memberPossible causes
(1) Stop valve of outdoor unit is closed during operation. (2) Disconnection or loose connection of connector (63L) on outdoor controller board (3) Disconnection or loose connection of 63L (4) Defective outdoor controller board (5) Leakage or shortage of refrigerant (6) Malfunction of linear expansion valve
Solution
Solution steps are not shared for faults that may be dangerous.
No do-it-yourself solution is given for this fault. For your safety, call an authorised service.
Remote technician support
Get help from a technician over a video call.
Address of this page: https://www.remfixit.com/tr/mitsubishi-electric/pac/ul