Error code
Mitsubishi Electric PAA code P6
No approved translation for this record yet; showing the original text.
Meaning
Specifications: Freezing/overheating protection is working 1. Freezing protection (Cooling mode) The unit is in six-minute resume prevention mode if pipe <liquid or condenser/evaporator> temperature stays under -15˚ C [5˚ F] for three minutes after the compressor started. Abnormal if it stays under -15˚ C [5˚ F] for three minutes again within 16 minutes after six-minute resume prevention mode. 2. Overheating protection (Heating mode) The units are in six-minute resume prevention mode if pipe < Liquid or condens
Member details
Signed-in members see the LED pattern and how to read the code with the remote control on eligible records.
View details as a memberPossible causes
(Cooling or drying mode) (1) Clogged filter (reduced airflow) (2) Short cycle of air path (3) Low-load (low temperature) operation beyond the tolerance range (4) Defective furnace fan motor • Fan motor is defective. • Indoor controller board is defective. 46
Solution
Solution steps are not shared for faults that may be dangerous.
No do-it-yourself solution is given for this fault. For your safety, call an authorised service.
Remote technician support
Get help from a technician over a video call.
Address of this page: https://www.remfixit.com/tr/mitsubishi-electric/paa/p6