Error code
Mitsubishi Electric PAA code P1
No approved translation for this record yet; showing the original text.
Meaning
Room temperature thermistor (TH1) 1. The unit is in three-minute resume prevention mode if short/ open of thermistor is detected. Abnormal if the unit does not reset normally after three minutes. (The unit returns to normal operation, if it has normally reset.) 2. Constantly detected during cooling, drying and heating operation Short: 90˚ C [194˚ F] or more Open: -40˚ C [-40˚ F] or less
Member details
Signed-in members see the LED pattern and how to read the code with the remote control on eligible records.
View details as a memberPossible causes
(1) Defective thermistor characteristics (2) Contact failure of connector (CN20) on the indoor controller board (Insert failure) (3) Breaking of wire or contact failure of thermistor wiring (4) Defective indoor controller board
Solution
Solution steps are available to members and are not shown on this page. Answer the questions to open the solution.
Remote technician support
Get help from a technician over a video call.
Address of this page: https://www.remfixit.com/tr/mitsubishi-electric/paa/p1