Meaning
(1) High discharging temperature Abnormal if compressor temperature 125: thermistor (TH4) exceeds or 110: continuously for 5 minutes. Abnormal if pressure detected by high pressure sensor and converted to saturation temperature exceeds 40: during defrosting and compressor temperature 110:. thermistor (TH4) exceeds (2) Refrigerant shortage abnormality When the conditions of below detecting 1 mode 1 or 2 are satisfied (1st detection) during the compressor operation, the compressor stops and restar
Member details
Signed-in members see the LED pattern and how to read the code with the remote control on eligible records.
View details as a memberPossible causes
Overheated compressor opera1 tion caused by shortage of refrigerant Defective operation of stop 2 valve Defective thermistor 3 4 Defective outdoor controller board Defective action of linear 5 expansion valve 1 Gas leakage, Gas shortage When heating operation, scant 2 refrigerant operation (When heating, airflow or thermo OFF are mixed-operation, it cause a refrigerant shortage operation.) 3 Ball valve performance failure (Not fully opened.) 4 Error detection of discharge super heat (1) High-pressure sensor defective (2) Discharge temperature thermistor defective (3) Thermistor input circuit defective and high-pressure sensor defective in multi controller board Error detection of TH7/TH3 5 (1) Thermistor defective (2) Thermistor input circuit defective in multi controller board
Solution
Solution steps are not shared for faults that may be dangerous.
No do-it-yourself solution is given for this fault. For your safety, call an authorised service.