Skip to content
RemFixitSearch fault code

Error code

Mitsubishi Electric klima code P6

No approved translation for this record yet; showing the original text.

Meaning

© 2025 Mitsubishi: Freezing/overheating protection is working 1. Freezing protection (Cooling mode) The unit is in six-minute resume prevention mode if pipe <liquid or condenser/evaporator> temperature stays under -15 ˚C [5 ˚F] for three minutes after the compressor started. Abnormal if it stays under -15 ˚C [5 ˚F] for three minutes again within 16 minutes after six-minute resume prevention mode. 2. Overheating protection (Heating mode) The units is in sixminute resume prevention mode if pipe <Liquid or condenser

Member details

Signed-in members see the LED pattern and how to read the code with the remote control on eligible records.

View details as a member

Possible causes

(Cooling or drying mode) (1) Clogged filter (reduced airflow) (2) Short cycle of air path (3) Low-load (low temperature) operation beyond the tolerance range (4) 4 Defective indoor fan motor • Fan motor is defective. • Indoor controller board is defective. (5) Defective outdoor fan control (6) Overcharge of refrigerant (7) Defective refrigerant circuit (clogs) (Heating mode) (3) Over-load (high temperature) operation beyond the tolerance range (4) Defective indoor fan motor • Fan motor is defective. • Indoor controller board is defective. (7) 7 Defective refrigerant circuit (clogs) (8) Bypass circuit of outdoor unit is defective 82 Specifications

Solution

Solution steps are not shared for faults that may be dangerous.

No do-it-yourself solution is given for this fault. For your safety, call an authorised service.

Remote technician support

Get help from a technician over a video call.