Mitsubishi Electric klima code FS

No approved translation for this record yet; showing the original text.

Meaning

function is For 10 mins after switched on.: freeze protection when THW1 detects 10 consecutive seconds a temp. ≤ 3ºC for 10 not be displayed if; disabled, water circulation pump1

Member details

Signed-in members see the LED pattern and how to read the code with the remote control on eligible records.

View details as a member

Possible causes

(1) Insufficient system head a or consecutive (2) Reduced flow in primary water circuit. Due to 1 or more of the following; Faulty pump, insufficient air purge, is blockedstrainer, leak in water circuit. (3) Valve operation fault (4) 2-way valve (field supply) actuator fault (5) 3-way valve actuator fault (6) THW1 has become detached from its holder. (7) THW1 or THW2 fault (8) FTC4 board failure

Solution

Solution steps are available to members and are not shown on this page. Answer the questions to open the solution.

Remote technician support

Get help from a technician over a video call.