Total capacity error Total capacity of indoor units in the same refrigerant system exceeds limitations. Error source: Outdoor unit
Member details
Signed-in members see the LED pattern and how to read the code with the remote control on eligible records.
View details as a memberPossible causes
(1) Total capacity of indoor units in the same refrigerant system exceeds the following: Model Total capacity PUHY-400 520 PUHY-500 650 PUHY-600 780 PUHY-650 845 PUHY-700 910 PUHY-750 975 (2) Erroneous setting of OC model selector switch (SW3-10). 1 2 3 4 5 6 7 8 9 10 .... ON 500, 250 ... OFF 400, 200 SW3
Solution
Solution steps are not shared for faults that may be dangerous.