Error code
Mitsubishi Electric klima code 6601
For your safety
This fault is rated high and involves an area that affects personal safety. No remote repair or do-it-yourself instructions are given; do not use the appliance or try to open or repair it.
Hazard area: mains voltage
Do not use the appliance and call an authorised service. If there is a risk to life, move to a safe place and see the emergency numbers.
The emergency numbers here are for Turkey. If you are outside Turkey, call your local emergency number.
No approved translation for this record yet; showing the original text.
Meaning
Troubleshooting III.: Communication error - Polarity unsettled 1. Error detected when the transmission processor which is an M-NET communication component cannot verify the + and - voltage polarity of the M-NET transmission line. 2. Detected invalid signal due to a transmission waveform error or noise on the M-NET transmission line. 3. Polarity not set error
Member details
Signed-in members see the LED pattern and how to read the code with the remote control on eligible records.
View details as a memberPossible causes
(1) There is no voltage between the M-NET transmission line connected to the AE-C/EW-C. (2) The M-NET transmission line connected to the AE-C/EW-C is shorted. (1) Contact failure of the transmission line of an outdoor unit or indoor unit. (2) Attenuation of the transmission voltage/signal because the allowable range for the transmission line wiring has been exceeded. • Farthest end: Exceeds 200 m (656 ft) • Remote controller line: Exceeds 10 m (32 ft) However, there is no problem if the portion where the remote controller line exceeds 10 m (32 ft) is 1.25 mm². (3) Attenuation of the transmission voltage/ signal because mismatch of transmission line types Wire diameter: Less than 1.25 mm² (4) The M-NET power supply is duplex feeding and has a same polarity connection. (5) Failure of control board in the outdoor unit (1) Defective AHC ADAPTER
Solution
Solution steps are not shared for faults that may be dangerous.
No do-it-yourself solution is given for this fault. For your safety, call an authorised service.
Address of this page: https://www.remfixit.com/tr/mitsubishi-electric/klima/6601