Error code
Mitsubishi Electric klima code 5102
No approved translation for this record yet; showing the original text.
Meaning
Pipe temperature sensor (TH22) fault (Indoor unit) Pipe temperature sensor (TH2) fault (OA processing unit): If a short or an open is detected during thermostat ON, the heat source unit turns to anti-restart mode for 3 minutes. When the error is not restored after 3 minutes (if restored, the heat source unit runs normally), the heat source unit makes an error stop. During heating operation During cooling operation for 3 minutes after the co | HIC bypass circuit outlet temperature sensor (TH2) fault (Heat source unit): When a short (high temperature intake) or an open (low temperature intake) of the thermistor is detected (the first detection), the heat source unit stops, turns to anti-restart mode for 3 minutes, and restarts when the detected temperature of the thermistor. When a short or an open is detected again (the second detection) after the first restart of the heat source unit, the heat source unit stops, turns to anti-restart mode for 3 minutes, and restarts in 3 minutes when the detected temperatur
Member details
Signed-in members see the LED pattern and how to read the code with the remote control on eligible records.
View details as a memberPossible causes
(1) Thermistor failure (2) Connector contact failure (3) Disconnected wire or partial disconnected thermistor wire (4) Unattached thermistor or contact failure (5) Indoor board (detection circuit) failure (2) Pinched lead wire (3) Torn wire coating (4) A pin on the male connector is missing or contact failure (5) Disconnected wire (6) Thermistor input circuit failure on the control board
Solution
Solution steps are not shared for faults that may be dangerous.
No do-it-yourself solution is given for this fault. For your safety, call an authorised service.
Remote technician support
Get help from a technician over a video call.
Address of this page: https://www.remfixit.com/tr/mitsubishi-electric/klima/5102