Mitsubishi Electric klima code 2135

No approved translation for this record yet; showing the original text.

Meaning

Water heat exchanger freeze up: 1) If either of the following conditions is detected (first detection) during operation, the heat source unit stops, goes into the 3minute restart delay mode, and automatically restarts after three minutes. Water outlet pipe temperature (TH8) of 4°C[39ºF] or below is detected. All of the following conditions are continuously met for one minute during Heating-only or Heating-main operation: Compressor frequency < Minimum frequency + 20 AND Evaporation temperature (Te) < -2ºC[28°F] AND Accumulator

Member details

Signed-in members see the LED pattern and how to read the code with the remote control on eligible records.

View details as a member

Solution

Solution steps are not shared for faults that may be dangerous.

No do-it-yourself solution is given for this fault. For your safety, call an authorised service.