Skip to content
RemFixitSearch fault code

Error code

Mitsubishi Electric klima code 2134

No approved translation for this record yet; showing the original text.

Meaning

Abnormal water temperature: 1) If a water inlet pipe temperature (TH7) of 5°C[41ºF] or below OR 50°C[122ºF] or above is detected (first detection) during operation, the heat source unit stops, goes into the 3-minute restart delay mode, and automatically restarts after three minutes. 2) If a water inlet pipe temperature (TH7) of 5°C[41ºF] or below OR 50°C[122ºF] or above is detected again (second detection) within 30 minutes of the first stoppage of the heat source unit, the unit will make an abnormal stop, and the error co

Member details

Signed-in members see the LED pattern and how to read the code with the remote control on eligible records.

View details as a member

Possible causes

(1) Heat source water circulation pump fault (2) Cooling tower or heater problem (3) Thermistor fault (TH7) (4) Thermistor signal input circuit fault on the control board (5) Improper installation of thermistor (TH7)

Solution

Solution steps are available to members and are not shown on this page. Answer the questions to open the solution.

Remote technician support

Get help from a technician over a video call.