Mitsubishi Electric klima code 1302

For your safety

This fault is rated high and involves an area that affects personal safety. No remote repair or do-it-yourself instructions are given; do not use the appliance or try to open or repair it.

Hazard area: mains voltage and refrigerant gas circuit

Do not use the appliance and call an authorised service. If there is a risk to life, move to a safe place and see the emergency numbers.

The emergency numbers here are for Turkey. If you are outside Turkey, call your local emergency number.

All emergency numbers and province details

No approved translation for this record yet; showing the original text.

Meaning

High pressure fault 1 (Heat source unit): 1) If the pressure of 3.78MPa [548psi] or higher is detected by the pressure sensor during operation (the first detection), the heat source stops once, turns to antirestart mode for 3 minutes, and restarts after 3 minutes automatically.

Member details

Signed-in members see the LED pattern and how to read the code with the remote control on eligible records.

View details as a member

Possible causes

(1) Indoor unit LEV actuation failure ĺ Heating (2) BC controller LEV malfunction Heating only or heating main : Indoor LEV 3 (3) BC controller SVM1 and 2 malfunction ->Cooling only (4) BC controller SVA and SVC malfunction ->Cooling only or cooling main (5) BC controller SVB malfunction ->Heating only or heating main (6) Heat source unit LEV7 actuation failure ĺCooling (7) Port address setting error. (8) Refrigerant service valve actuation failure (9) Short cycle on the indoor unit side (10) Clogged filter on the indoor unit (11) Reduced air flow due to dirty fan on the indoor unit fan (12) Dirty heat exchanger of the indoor unit (13) Insufficient heat source water flow (14) Heat source water supply cutoff (15) Dirty or clogged water heat exchanger Items (13) through (15) above reduce the condensing capability of the unit, resulting in high-pressure rise during heating operation. (16) Solenoid valve (SV1a) malfunction The by-pass valve (SV1a) can not control rise in high pressure. (17) Thermistor failure (TH3, TH7) (18) Pressure sensor failure (19) Failure of the thermistor input circuit and pressure sensor input circuit on the controller board (20) Thermistor mounting problem (TH3, TH7) (21) Disconnected male connector on the pressure switch (63H1) or disconnected wire (22) Voltage drop caused by unstable power supply voltage (1) Inner pressure drop due to a leakage. (2) Pressure sensor failure (3) Shorted-circuited pressure sensor outer rubber (4) A pin on the male connect

Solution

Solution steps are not shared for faults that may be dangerous.

No do-it-yourself solution is given for this fault. For your safety, call an authorised service.