Error code
Mitsubishi Electric CMB code 7100
No approved translation for this record yet; showing the original text.
Meaning
Total capacity error Total capacity of indoor units in the same refrigerant system exceeds limitations. Trouble source: Outdoor unit
Member details
Signed-in members see the LED pattern and how to read the code with the remote control on eligible records.
View details as a memberPossible causes
(1) Total capacity of indoor units in the same refrigerant system exceeds the following: Model Total capacity Total capacity code PURY-(P)200 302 62 PURY-(P)250 378 78 PU(H)Y-(P)200 260 52 PU(H)Y-(P)250 325 65 (2) Erroneous setting of OC model selector switch (SW3-10). ON ..... 250 OFF ... 200 1 2 3 4 5 6 7 8 9 10 SW3
Solution
Solution steps are not shared for faults that may be dangerous.
No do-it-yourself solution is given for this fault. For your safety, call an authorised service.
Remote technician support
Get help from a technician over a video call.
Address of this page: https://www.remfixit.com/tr/mitsubishi-electric/cmb/7100