Error code
Mitsubishi Electric CMB code 5111
No approved translation for this record yet; showing the original text.
Meaning
Liquid inlet (TH11) Bypass outlet controlled) (TH12) HEX inlet liquid level detecting (BC (TH13) abnormality HEX outlet liquid level detecting (TH14) sensor Bypass inlet Thermal (TH15) Intermediate section (TH16): 1. When short (high temp. inlet) or open (low temperature inlet) of thermistor is detected during operation, error stop will be commenced displaying “5111” or “5112”, “5113” or “5114”, or “5115” or “5116. 2. The above detectection is not made during defrostig and 3minute after changing operation mode.
Member details
Signed-in members see the LED pattern and how to read the code with the remote control on eligible records.
View details as a memberPossible causes
(1) Thermistor trouble. (2) Biting of lead wire. (3) Broken cover. (4) Coming off of pin at connector portion, poor contact. (5) Broken wire. (6) Faulty thermistor input circuit of control board. Short Detected TH11 110°C or more (0.4 kΩ) TH12 110°C or more (0.4 kΩ) TH13 – TH14 110°C or more (1.14 kΩ) TH15 70°C or more (1.14 kΩ) TH16 70°C or more (0.4 kΩ)
Solution
Solution steps are available to members and are not shown on this page. Answer the questions to open the solution.