Error code
Mitsubishi Electric CMB code 5103
No approved translation for this record yet; showing the original text.
Meaning
Gas-side pipe temperature sensor (TH23) fault (Indoor unit) Gas-side pipe temperature sensor (TH3) fault (OA processing unit): If a short or an open is detected during thermostat ON, the outdoor unit turns to anti-restart mode for 3 minutes. When the error is not restored after 3 minutes (if restored, the outdoor unit runs normally), the outdoor unit makes an error stop. During heating operation During cooling operation for 3 minutes after the compressor turns | Heat exchanger outlet temperature sensor (TH3) fault (Outdoor unit): When a short (high temperature intake) or an open (low temperature intake) of the thermistor is detected (the first detection), the outdoor unit stops, turns to anti-restart mode for 3 minutes, and restarts when the detected temperature of the thermistor. When a short or an open is detected again (the second detection) after the first restart of the outdoor unit, the outdoor unit stops, turns to anti-restart mode for 3 minutes, and restarts in 3 minutes when the detected temperature is within th
Member details
Signed-in members see the LED pattern and how to read the code with the remote control on eligible records.
View details as a memberPossible causes
(1) Thermistor failure (2) Connector contact failure (3) Disconnected wire or partial disconnected thermistor wire (4) Unattached thermistor or contact failure (5) Indoor board (detection circuit) failure (2) Pinched lead wire (3) Torn wire coating (4) A pin on the male connector is missing or contact failure (5) Disconnected wire (6) Thermistor input circuit failure on the control board
Solution
Solution steps are not shared for faults that may be dangerous.
No do-it-yourself solution is given for this fault. For your safety, call an authorised service.
Remote technician support
Get help from a technician over a video call.
Address of this page: https://www.remfixit.com/tr/mitsubishi-electric/cmb/5103