Mitsubishi Electric CMB code 3152
No approved translation for this record yet; showing the original text.
Meaning
Abnormal temperature inside the Inverter control box: 1. If the temperature inside the con70°C trol box is detected to be or more during operation (the first time it is detected), the heat source unit is stopped temporarily, the system enters the 3-minute restart prevention mode, then restarts the heat source unit after 3 minutes. 2. If the temperature inside the con70°C trol box is detected to be or more during operation (the second time it is detected) again within 30 minutes after the heat source unit stops according to 1. above, an abnormal sto
Member details
Signed-in members see the LED pattern and how to read the code with the remote control on eligible records.
View details as a memberPossible causes
(1) Cooling air passage closed. (2) Rise in the ambient temperature. (3) Faulty power transistor. (4) Faulty thermistor (5) Faulty thermistor input circuit on the control board. (6) Faulty cooling fan, connector pulled out. (7) Faulty LEV 1 for inverter cooling, connector pulled out. (8) Faulty cooling fan output circuit on the relay board. (9) Faulty cooling fan output circuit on the control board. 10)Faulty LEV 1 output circuit for inverter cooling on the control board.