Mitsubishi Electric CMB code 2135

No approved translation for this record yet; showing the original text.

Meaning

Freezing of the water heat exchanger.: 1. If the water heat exchanger freeze prevention thermostat op3±1°C) erates (OFF at (the first time) the heat source unit stops temporarily enters the 3-minute restart prevention mode, the restarts after 3 minutes. 2. If the water heat exchanger freeze prevention thermostat op3±1°C) erates (OFF at again (the second time) within 30 minutes after the heat source units stops according to 1. above, an abnormal stop is performed and at that time, “2135” is displayed. 3. If the water heat exchanger fr

Member details

Signed-in members see the LED pattern and how to read the code with the remote control on eligible records.

View details as a member

Possible causes

(1) Failure of the heat source water circulating pump to operate. (2) Heating equipment out of order (3) Clogged or dirty water heat exchanger (4) Lead wire to the water heat exchanger freeze prevention thermostat is disconnected. (5) Connector to the water heat exchanger freeze prevention thermostat is pulled out. (6) Faulty water heat exchanger freeze prevention thermostat input circuit on the relay board. (7) Faulty water heat exchanger freeze prevention thermostat input circuit on the control board.

Solution

Solution steps are available to members and are not shown on this page. Answer the questions to open the solution.