Skip to content
RemFixitSearch fault code

Error code

Mitsubishi Electric CMB code 1500

No approved translation for this record yet; showing the original text.

Meaning

Overchanged refrigerant abnormality: 1. 2. When liquid level of accumulator reaches AL=2 (overflow level) and Td-Tc 20 deg again (the second time), error stop is observed with code No.“1500” displayed. 3. When liquid level of accumulator reaches AL=2 (overflow level) and Td-Tc 20 deg 30 or more minutes after stop of h

Member details

Signed-in members see the LED pattern and how to read the code with the remote control on eligible records.

View details as a member

Possible causes

(1) Excessive refrigerant charge. (2) Broken wire of liquid level heater. (3) Poor heater output caused by control circuit board trouble. (4) Thermistor trouble. (TH2, TH3, TH4) (5) Thermistor input circuit trouble on control circuit board . (6) Poor mounting of thermistor. (TH2, TH3, TH4) (4) 30 minutes after stop of heat source unit is intermittent fault check period with LED displayed.

Solution

Solution steps are not shared for faults that may be dangerous.

No do-it-yourself solution is given for this fault. For your safety, call an authorised service.

Remote technician support

Get help from a technician over a video call.