Error code
DAIKIN ERX100~140A8V3, ERX125~250A7W1 code E7
No approved translation for this record yet; showing the original text.
Meaning
Outdoor Unit: Malfunction of Outdoor Unit Fan Motor
Member details
Signed-in members see the LED pattern and how to read the code with the remote control on eligible records.
View details as a memberPossible causes
m When the fan runs with speed less than a specified one for 6 seconds or more when the fan motor running conditions are met m When connector detecting fan speed is disconnected (only ERX125~250A7W1) m When malfunction is generated 4 times, the system shuts down. m Malfunction of fan motor m The harness connector between fan motor and PC board is left in disconnected, or faulty connector m Fan does not run due to foreign matters tangled m Clearing condition: Operate for 5 minutes (normal)