Error code
DAIKIN 5 Troubleshooting Outdoor unit RXYTQ-T Diagnosis Counter- measures 2 Method for Detecting Malfunction Detect malfunction code E5
No approved translation for this record yet; showing the original text.
Meaning
Inverter Compressor Lock
Member details
Signed-in members see the LED pattern and how to read the code with the remote control on eligible records.
View details as a memberPossible causes
NO NO YES NO NO YES YES NO YES NO YES YES U V W A Check in Monitor Mode 14~20 hp classes are equipped with two compressors. (For the checking procedure, refer to information on ‘5 - 3.3.3 Check for descriptions of malfunctions/retries’.) Is the stop valve open? Are wire connections made according to the Wiring Diagram? The insulation resistance of the relevant compressor is low (< 100kΩ) normal > 1 Mohm. The relevant compressor has a wiring disconnection in it. Go to the next page. For Compressor 1 Connection wiring on the M1C side For Compressor 2 Connection wiring on the M2C side Power OFF Is the connection line of the relevant compressor normal? Are wire connections made to phases U, V and W in the proper order and manner? Make proper wire connections. Make proper wire connections.
Solution
Solution steps are not shared for faults that may be dangerous.
No do-it-yourself solution is given for this fault. For your safety, call an authorised service.