ComAp jeneratör senkronizasyon paneli All models error codes
Codes
- 1-121Error codeIndication of error in communication with binary inputs extension module. Check if the unit with corresponding CAN address is - powered up - address of the module is set correctly (see Modules card in GenConfig and an extension module manual) - correctly connected and check connection of terminating resistors on the CAN1 bus (see IGS- NT Installation Guide, External modules connection chapter) - the CAN bus Low and High wires are not swapped To check module communication activity look at the Tx and Rx LEDs of the CAN bus port. Fast flashing means that communication is OK
- B01Error codeNominal Voltage Ph-N
- B02Error codeNominal Voltage Ph-Ph
- B03Error codeThreshold for Generator Underfrequency alarm, relative to the nominal frequency (setpoint B03 Nominal Frequency)
- B04Error codeNominal system voltage (phase to phase). This setpoint can be hidden depending on the connection type (setpoint B04 Connection Type).You can setup this value only if you will choose the connection type as 3Ph3Wire or 3Ph4Wire - B04 Connection Type (3;4)
- B05Error codeNominal system voltage (phase to neutral). This setpoint can be hidden depending on the connection type (setpoint B05 Connection Type). You can setup this value only if you will choose the connection type as Mono phase or Split phase - B05 Connection Type (1;2)
- B08Error codeWhen this setpoint is enabled, the controller is switched to special operation mode. First screen was changed and generator voltage measurement is hides in this operation mode. Setpoint code Value Meaning B08 1 Disable B08 2 Enable First main screen shows battery voltage, running hours and engine status (stop, starting/stopping, run) via symbol in light tower reflector (upper left corner). Second screen shows all analog values which are available. (Oil Pressure, Coolant Temperature; Fuel Level and Battery Voltage) Last screen is event log
- B09Error codeNominal Current
- E04Error codeOil Pressure Shutdown
- E05Error codeCoolant Temperature Shutdown
- E08Error codeOil Pressure Starter Disengagement
- G05Error codeGenerator Short Circuit Shutdown
- G06Error codeGenerator Short Circuit Delay
- G07Error codeGenerator Overload Shutdown
- G08Error codeGenerator Overload Delay
- I22Error codeWhen this setpoint is enabled, the controller will use I22 Low Oil Pressure or I23 Oil Pressure Analog signal for starter disengagement. Starter will be disengaged when oil pressure reach starting oil pressure or binary input I22 Low Oil Pressure will be opened (Normally Open contact) or closed (Normally Closed contact). When is disabled then only RPM (frequency), generator voltage or D+ will be used for starter disengagement. Setpoint code Value Meaning E08 1 Disable E08 2 Enable
- I23Error codeOil Pressure Analog
- I25Error codeCoolant Temperature Analog
- L1Error codeGenerator L1, L2 or L3 voltage was under the Gen <V BOC limit for Gen V del time. Undervoltage protections are based on Gener protect: Gen <V BOC and Gen V del setpoints. This alarm is issued if voltage protections are based on phase to neutral voltages. It means that Basic 19 settings: FixVoltProtSel is set to PHASE-NEUTRAL
- L12Error codeGenerator L12, L23 or L31 voltage was under the Gen <V BOC limit for Gen V del time.. Undervoltage protections are based on Gener protect: Gen <V BOC and Gen V del setpoints. This alarm is issued if voltage protections are based on phase to phase voltages. It means that Basic 19 settings: FixVoltProtSel is set to PHASE-PHASE
- L23Error codeIf the value of 10 min. average mains voltage of any phase (Mains Avg V1, Mains Avg V2, Mains Avg V3) exceed value given by setpoint Mains Avg >V MP (Mains protect group) the MCB is opened and message Mains Avg x >V appears in alarm list and history record. BO Common MP is activated (x indicates number of phase)
- Ug1Error codeGenerator voltage: Ug1>, Ug1<, Ug2>, Ug2<, Ug3>, Ug3<