Cummins PowerCommand generator kontrol paneli All models error codes
Codes
- Aux101Error codeSelects the type of analog input sensor. (Password level: 1) Allowed values: Default, Do Nothing (Default: Do Nothing)
- Aux102Error codeSelects discrete input fault/event for this input (Password level: 1) Allowed values: Default, Do Nothing, Low Fuel in Day Tank Switch, Low Coolant Switch #2, High Alt Temperature Switch, Ground Fault Switch, Exercise Switch, Battle Short Switch, Battery Charger Failed Switch, Low Engine Temperature Switch, Speed Droop Enable Switch, Voltage Droop Enable Switch, Rated/Idle Switch, AMM In Auto, Low Fuel Pressure Switch, Start Signal Integrity Switch. (Default: Do Nothing)
- DS6Error codeThis LED is on if event 1483 (Common Alarm) is active
- F4Error codeElectronic Pressure Regulator
- FC1441Error codeSets the genset response for fault code 1441. (Password level: 1.) Allowed values: None, Warning, Shutdown. (Default: Warning.)
- han24Error code
- HMI113Error codeSelects the genset reaction to a loss of an Annunciator as critical or non-critical. Selecting Critical will cause a shutdown when the Annunciator loses communication. (Password level: 1.) Allowed values: Critical Device Response, Non-Critical Device Response. (Default: Non-Crit Device Resp.)
- HMI220Error codeSelects the genset reaction to a loss of an HMI220 Operator Panel as critical or non-critical. A critical response will shutdown the genset when PCCnet communication is lost. (Password level: 1.) Allowed values: Critical Device Response, Non-Critical Device Response. (Default: Non-Crit Device Resp.)
- HMI320Error codeSelects the genset reaction to a loss of an HMI320 Operator Panel as critical or non-critical. A critical response will shutdown the genset when PCCnet communication is lost. (Password level: 1.) Allowed values: Critical Device Response, Non-Critical Device Response. (Default: Non-Crit Device Resp.)
- J10Error codeVoltage sources, current sources
- J10-3Error codeCurrent source 1
- J10-4Error codeCurrent source 2
- J10-5Error codeCurrent source 3
- J10-6Error codeCurrent source 4
- J10-7Error codeVoltage source 1
- J10-8Error codeVoltage source 2
- J10-9Error codeGround for current source or voltage source
- J10-10Error codeGround for current source or voltage source
- J10-11Error codeGround for current source or voltage source
- J10-12Error codeGround for current source or voltage source
- J11-1Error codeOil Pressure Sender (active) +5 V
- J11-2Error code
- J11-3Error code
- J11-13Error codeOil Temp Sensor
- J11-14Error codeOil Temp Sensor Return
- J12Error code4; L2: J12-2, J12-5;
- J20Error code17 will activate the alarm at the control
- J20-16Error codeOil Priming Pump Driver
- J22Error code2; L3, J2-3; LN, J22-4) to the Ground Fault Alarm Relay (Input 6 and 8), correct if faulty
- J25Error code6 Ground) disables the E-Stop alarm. An open circuit should activate the E-Stop
- J29-10Error codeFault Reset
- L1Error codeMonitors the genset L1 current value
- L1LError codeGenset L1L2 voltage
- L1NError codeGenset L1N voltage
- L2Error codeGenset L2 current
- L2LError codeGenset L2L3 voltage
- L2NError codeGenset L2N voltage
- L3Error codeGenset L3 current
- L3LError codeGenset L3L1 voltage
- L3NError codeGenset L3N voltage
- L12Error codeGenset L12 voltage Calibration trim (Password level: 1.) Allowed values: 90~110 %. (Default: 100 %.)
- L23Error codeGenset L23 voltage Calibration trim (Password level: 1.) Allowed values: 90~110 %. (Default: 100 %.)
- L31Error codeGenset L31 voltage Calibration trim (Password level: 1.) Allowed values: 90~110 %. (Default: 100 %.)
- ort10Error codeMonitor point for the Exhaust Port 10 Temperature Allowed values: -460~3155 degF
- ort11Error codeMonitor point for the Exhaust Port 11 Temperature Allowed values: -460~3155 degF
- ort12Error codeMonitor point for the Exhaust Port 12 Temperature Allowed values: -460~3155 degF
- ort13Error codeMonitor point for the Exhaust Port 13 Temperature Allowed values: -460~3155 degF
- ort14Error codeMonitor point for the Exhaust Port 14 Temperature Allowed values: -460~3155 degF
- ort15Error codeMonitor point for the Exhaust Port 15 Temperature Allowed values: -460~3155 degF
- ort16Error codeMonitor point for the Exhaust Port 16 Temperature Allowed values: -460~3155 degF