ACS Klima ERV All models error codes
Codes
- 4-1Error codeCu cable mm2
- 7Error codeAI1 LOSS
- 8Error codeAI2 LOSS
- 14Error codeEXT FAULT 1
- 15Error codeEXT FAULT 2
- 16Error codeEARTH FAULT
- 20Error codeOPEX PWR
- 26Error codeDRIVE ID
- 31Error codeEFB 1
- 2001Error codeCurrent limiting controller is active. Check for and correct: • Excessive motor load. • Insufficient acceleration time (parameters 2202 ACCELER TIME 1 and 2205 ACCELER TIME 2). • Faulty motor, motor cables or connections
- 2002Error codeOvervoltage controller is active. • Insufficient deceleration time (parameters 2203 DECELER TIME 1 and 2206 DECELER TIME 2)
- 2003Error codeUndervoltage controller is active.
- 2004Error codeThe change in direction being attempted is not allowed. Either: • Do not attempt to change the direction of motor rotation, or • Change parameter 1003 DIRECTION to allow direction change (if reverse operation is safe)
- 2005Error codeFieldbus communication has timed out. Check for and correct: • Fault setup (3018 COMM FAULT FUNC and 3019 COMM FAULT TIME). • Communication settings (Group 51: EXT COMM MODULE or Group 53: EFB PROTOCOL as appropriate). • Poor connections and/or noise on line
- 2006Error codeAnalog input 1 is lost, or value is less than the minimum setting. Check: • Input source and connections. • Parameter that sets the minimum (3021). • Parameter that sets the alarm/fault operation (3001)
- 2007Error codeAnalog input 2 is lost, or value is less than the minimum setting. Check: • Input source and connections. • Parameter that sets the minimum (3022). • Parameter that sets the alarm/fault operation (3001)
- 2008Error codePanel communication is lost and either: • Drive is in local control mode (the control panel displays LOC), or • Drive is in remote control mode (REM) and is parameterized to accept start/stop, direction or reference from the control panel. To correct check: • Communication lines and connections. • Parameter 3002 PANEL COMM ERR. • Parameters in Group 10: START/STOP/DIR and Group 11: REFERENCE SELECT (if drive operation is REM)
- 2009Error codeDrive heatsink is hot. This alarm warns that a DEVICE OVERTEMP fault may be near. R1…R4: 100 °C (212 °F) R5, R6: 110 °C (230 °F) Check for and correct: • Fan failure. • Obstructions in the air flow. • Dirt or dust coating on the heat sink. • Excessive ambient temperature. • Excessive motor load
- 2010Error codeMotor is hot, based on either the drive’s estimate or on temperature feedback. This alarm warns that a MOT OVERTEMP fault trip may be near. Check: • Check for overloaded motor. • Adjust the parameters used for the estimate (3005…3009). • Check the temperature sensors and Group 35: MOTOR TEMP MEAS
- 2012Error codeMotor is operating in the stall region. This alarm warns that a MOTOR STALL fault trip may be near
- 2013Error codeThis alarm warns that the drive is about to perform an automatic fault reset, which may start the motor. • To control automatic reset, use Group 31: AUTOMATIC RESET
- 2014Error codeThis alarm warns that the PFC autochange function is active. • To control PFC, use Group 81: PFC CONTROL and the PFC macro on page 80
- 2015Error codeThis alarm warns that the PFC interlocks are active, which means that the drive cannot start the following: • Any motor (when Autochange is used). • The speed regulated motor (when Autochange is not used)
- 2018Error codeThis alarm warns that the PID sleep function is active, which means that the motor could accelerate when the PID sleep function ends. • To control PID sleep, use parameters 4022…4026 or 4122…4126
- 2021Error codeThis alarm warns that the Start Enable 1 signal is missing. • To control Start Enable 1 function, use parameter 1608. To correct, check: • Digital input configuration. • Communication settings
- 2022Error codeThis alarm warns that the Start Enable 2 signal is missing. • To control Start Enable 2 function, use parameter 1609. To correct, check: • Digital input configuration. • Communication settings
- 2023Error codeEmergency stop activated
- 2024Error codeThe drive is not detecting a valid encoder signal. • Voltage logic levels are outside of the specified range. • A working and properly connected Pulse Encoder Interface Module, OTAC-01. • Wrong value entered in parameter 5001 PULSE NR. A wrong value will only be detected if the error is such that the calculated slip is greater than 4 times the rated slip of the motor. • Encoder is not being used, but parameter 5002 ENCODER ENABLE = 1 (ENABLE)
- 2025Error codeSignals that a the drive is performing a First Start evaluation of motor characteristics. This is normal the first time the motor is run after motor parameters are entered or changed. See parameter 9910 ID RUN for a description of motor models
- 2027Error codeThis alarm warns that the condition defined by parameter 3701 USER LOAD C MODE has been valid longer than half of the time defined by 3703 USER LOAD C TIME
- 2028Error codeShown during the Start delay. See parameter 2113 START DELAY
- 5002Error codeThe communication profile is incompatible with the drive
- 5014Error codeButton is disabled, because drive is faulted
- 5031Error codeDrive is not ready, e.g due to low DC voltage
- 5032Error codeParameter error was detected
- 5040Error codeSelected parameter set can’t be found in the current parameter backup
- 5042Error codeSelected parameter set can’t be found in the current parameter backup
- 5051Error codeFile error was detected
- 5070Error codePanel backup memory write error was detected
- 5071Error codePanel backup memory read error was detected
- 5081Error codeOperation is not allowed, because a fault is active
- 5088Error codeOperation failed, because a drive memory error was detected
- 5089Error codeDownload failed, because a CRC error was detected
- 5090Error codeDownload failed, because a data processing error was detected
- 5091Error codeOperation failed, because a parameter error was detected
- ACS550Error codeInput current A
- RJ-45Error code8 Control panel (RJ-45) Modbus RTU Screen 1 SCR (RS-232) 2 AI1 S1 AO 7 Analog input 1 Analog output AI1 AI2 0…10 V 0…20 mA 3 GND mA GND 8 Reference voltage V 4 +10V 10 V DC, max. 10 mA Analog input 2 5 AI2 6 GND Aux. voltage output 9 +24 V PROGRAMMABLE RE 4 V DC, max.
- S1ParameterUser 1 macro loaded into use. Before loading, check that the saved parameter settings and the motor model are suitable for the application
- S2ParameterUser 2 macro loaded into use. Before loading, check that the saved parameter settings and the motor model are suitable for the application
- U1Error codeThe output Voltage in volts